ICD 13—Standard Controller ICD-13/05 1 of 56
Gemini
Controls
Group
Interface
Control
Document
ICD 13—Standard Controller
Bret Goodrich, Andrew Johnson and Corinne Boyer
ICD-13/05
This document describes the VME hardware and software which
makes up a Gemini Standard Controller.
1.0 Introduction
1.1 Purpose
This document describes the hardware and software for the Gemini Standard Controller,
comprising the basic enclosure and VME cards needed to make up an EPICS system for
use at the Gemini telescopes. This document will be used while specifying and costing
the IOC, and also after the goods are delivered to set them up and perform a brief accep-
tance test.
1.2 Scope
The document supersedes previous hardware descriptions of the Standard Instrument
Controller (SIC) work package, specifically [1]. Later revisions of this document will
also supersede SIC software descriptions [2].
1.3 Applicable Document
The following documents are referenced in the text. They should be read when further
information is required on a topic.
[1] Hardware Installation, Andrew Johnson, RGO.
[2] Software Installation, Andrew Johnson, RGO.
[3] Microcomputer Packaging, Edition 1, Elma Electronics.
[4] MVME712 Transition Module and P2 Adapter Board Users Manual, Motorola
Computer Group, MVME712M/D2A2.
[5] MVME167 Single Board Computer Installation Guide, Motorola Computer
Group, MVME167IG/D3.
Seitenansicht 0
1 2 3 4 5 6 ... 55 56

Inhaltsverzeichnis

Seite 1 - ICD 13—Standard Controller

Created:July 20, 1994Modified:September 27, 2001ICD 13—Standard Controller ICD-13/05 1 of 56GeminiControlsGroupInterfaceControlDocumentICD 13—Standard

Seite 2 - Introduction

Transition Module10 of 56 ICD-13/05 ICD 13—Standard ControllerInstall the VME enclosure in the desired workplace, generally a 19’ rack. If installed i

Seite 3 - Courier font

Transition ModuleICD 13—Standard Controller ICD-13/05 11 of 56..5.2 Installation of the MVME712-MThe MVME712-M transition module has two boards, a sma

Seite 4

VME Single Board Computer12 of 56 ICD-13/05 ICD 13—Standard Controllernated when the SBC has power. If either LED fails to light there may be a proble

Seite 5 - /05 5 of 56

VME Single Board ComputerICD 13—Standard Controller ICD-13/05 13 of 56• MVME167 Single Board Computer User’s ManualSimilar to the Installation Guide,

Seite 6

VME Single Board Computer14 of 56 ICD-13/05 ICD 13—Standard ControllerThe testing procedure is as follows:1. Switch off the enclosure DC supply.2. Rem

Seite 7 - /05 7 of 56

VME Single Board ComputerICD 13—Standard Controller ICD-13/05 15 of 56• Another short pause, then:MPU Clock Speed =33Mhz167-Bug>• The FAIL LED also

Seite 8

VME Single Board Computer16 of 56 ICD-13/05 ICD 13—Standard ControllerAlthough the VMEbus makes no distinction between which slot a card can be instal

Seite 9 - 4.0 VME Enclosure

Time Bus Interface CardICD 13—Standard Controller ICD-13/05 17 of 567.0 Time Bus Interface CardAny IOC which is required to know the absolute time to

Seite 10 - 5.0 Transition Module

Time Bus Interface Card18 of 56 ICD-13/05 ICD 13—Standard Controller3. Switch on the enclosure power. The displays may initially show a random number,

Seite 11 - Item Description

Synchro Bus Interface CardICD 13—Standard Controller ICD-13/05 19 of 56In the above, XXXX can be any value, and the BCD digits HH and MMSS should be t

Seite 12 - 6.0 VME Single Board Computer

Introduction2 of 56 ICD-13/05 ICD 13—Standard Controller[6] MVME167BUG User’s Manual, Motorola Computer Group, MVME167BUG.[7] ICD 9-EPICS Time Bus Dri

Seite 13

Synchro Bus Interface Card20 of 56 ICD-13/05 ICD 13—Standard Controllerinstalled for the second (right) slot. It is good practice to do this even if t

Seite 14 - • After a short pause:

Synchro Bus Interface CardICD 13—Standard Controller ICD-13/05 21 of 561. Install the module, leaving the dust guards on the fiber transmitter and rec

Seite 15 - • Another short pause, then:

DC Servo Motor Controller22 of 56 ICD-13/05 ICD 13—Standard Controller167-Diag>MD F0200000:3F0200000 XX27 40XX NNE5 .’@XX.6.In the above, XX could

Seite 16

Stepper Motor ControllerICD 13—Standard Controller ICD-13/05 23 of 562. The following sends the command ‘VER’ to the card, which the DSP will respond

Seite 17 - 7.0 Time Bus Interface Card

Stepper Motor Controller24 of 56 ICD-13/05 ICD 13—Standard Controller• Home Input• +5V and Ground10.1 DescriptionThe Standard Controller stepper motor

Seite 18 - Jumper Setting Type

Stepper Motor ControllerICD 13—Standard Controller ICD-13/05 25 of 561. Demonstrate that the card registers respond to accesses from the VMEbus as fol

Seite 19 - Synchro Bus Interface Card

Stepper Motor Controller26 of 56 ICD-13/05 ICD 13—Standard ControllerFFFFFC01 0A? =FFFFFC01 0D?FFFFFC01 56?FFFFFC01 4D?FFFFFC01 45?FFFFFC01 38?FFFFFC0

Seite 20

TTL I/O CardICD 13—Standard Controller ICD-13/05 27 of 56To run the program type G E000. Use the terminal’s Break key or the MVME167ABORT button to re

Seite 21

TTL I/O Card28 of 56 ICD-13/05 ICD 13—Standard Controllerinput signals (connector JK1), and ports 4 to 7 as outputs (JK2), and does not supportthe use

Seite 22 - 9.0 DC Servo Motor Controller

TTL I/O CardICD 13—Standard Controller ICD-13/05 29 of 56FFFFD086 0010? 20FFFFD086 0020? 40FFFFD086 0040? 80FFFFD086 0080? 100FFFFD086 0100? 200FFFFD0

Seite 23 - 10.0 Stepper Motor Controller

Standard Controller InformationICD 13—Standard Controller ICD-13/05 3 of 56SIC Standard Instrument ControllerVME Versa Module EuropeWRS Wind River Sys

Seite 24 - • +5V and Ground

Digital Output Module30 of 56 ICD-13/05 ICD 13—Standard Controller12.0 Digital Output ModuleA Digital Output card is also available for driving higher

Seite 25 - /05 25 of 56

Digital Output ModuleICD 13—Standard Controller ICD-13/05 31 of 56All I/O signals emerge from the front panel of the card. As these are Open-Collector

Seite 26

Analog Input Module32 of 56 ICD-13/05 ICD 13—Standard Controller13.0 Analog Input ModuleAn Analog input module supports either 32 channels of Single-e

Seite 27 - 11.0 TTL I/O Card

Analog Input ModuleICD 13—Standard Controller ICD-13/05 33 of 56The card inputs are all connected to the front-panel connector JK1, for which thepinou

Seite 28 - • PASS on, FAIL off

Analog Input Module34 of 56 ICD-13/05 ICD 13—Standard ControllerFFFF6081 81? 82• Both On.FFFF6081 82? 83.• PASS On, FAIL Off.3. Read the card identifi

Seite 29

Analog Output ModuleICD 13—Standard Controller ICD-13/05 35 of 56It is not a simple matter to get the card to execute an analog conversion, thus it is

Seite 30 - 12.0 Digital Output Module

Analog Output Module36 of 56 ICD-13/05 ICD 13—Standard Controllerconnector required for this socket is manufactured by Panduit, part number 120-332-43

Seite 31

Data LANICD 13—Standard Controller ICD-13/05 37 of 562. To set the output voltages for measurement using a multimeter, write a 16-bit valueto the card

Seite 32 - 13.0 Analog Input Module

Data LAN38 of 56 ICD-13/05 ICD 13—Standard Controller• CPU: Baja4700-175-16MB-1FL• PMC card: 1409002• Serial/Ethernet cable: 340A003-54• Fast ethernet

Seite 33 - • Both Off

Other EPICS-supported VME CardsICD 13—Standard Controller ICD-13/05 39 of 5616.0 Other EPICS-supported VME CardsThe information in the table below was

Seite 34 - • PASS On, FAIL Off

Standard Controller Information4 of 56 ICD-13/05 ICD 13—Standard ControllerThe Standard Controller includes the VME chassis and associated cards shown

Seite 35 - 14.0 Analog Output Module

Other EPICS-supported VME Cards40 of 56 ICD-13/05 ICD 13—Standard Controllerepics_applications” in the body of an email to [email protected]. Anoth

Seite 36

Software InstallationICD 13—Standard Controller ICD-13/05 41 of 5617.0 Software InstallationThe following sections describe the installation of the so

Seite 37 - 15.0 Data LAN

VxWorks42 of 56 ICD-13/05 ICD 13—Standard Controller18.0 VxWorksThe Gemini work packages currently use Wind River Systems VxWorks version 5.2.Each sit

Seite 38 - • PMC card: 1409002

VxWorksICD 13—Standard Controller ICD-13/05 43 of 56ln -s vxworks5.2 vxworkscd vxworks3.Read the VxWorks system tape from the drive using tar. This wi

Seite 39 - Supplier Model Function

VxWorks44 of 56 ICD-13/05 ICD 13—Standard Controller‘.’ = clear field; ‘-’ = go to previous field; ^D = quitboot device : eiprocessor number : 0host n

Seite 40

VxWorksICD 13—Standard Controller ICD-13/05 45 of 56#define INCLUDE_NFS /* nfs package */#define INCLUDE_PING /* ping() utility */#define INCLUDE_POSI

Seite 41 - 17.0 Software Installation

VxWorks46 of 56 ICD-13/05 ICD 13—Standard Controllerhorse% mkdir vwhorse% cd vw/home/epics/vwhorse% ln -s /opt/local/epics/vxworks/{bin,lib,src,h,man}

Seite 42 - 18.0 VxWorks

EPICSICD 13—Standard Controller ICD-13/05 47 of 56horse% /usr/ccs/bin/makemake -f Makefile.MC68040gnu CPU=MC68040 TOOL=gnu vxWorkscc68k -c -O -fvolati

Seite 43

EPICS48 of 56 ICD-13/05 ICD 13—Standard Controller19.1 PreliminariesThere should be an account named epics on your host system. This account will cont

Seite 44

EPICSICD 13—Standard Controller ICD-13/05 49 of 56Channel Access variables for the logging server and the NTP server.cd $EPICS/extensions/src/uaevi st

Seite 45

Standard Controller InformationICD 13—Standard Controller ICD-13/05 5 of 56TABLE 1. Gemini Standard Controller Hardware ComponentsComponentManufacture

Seite 46

EPICS50 of 56 ICD-13/05 ICD 13—Standard Controlleraround the address. If there are any other site-specific issues for your VxWorks sys-tems they shoul

Seite 47 - 19.0 EPICS

CapFastICD 13—Standard Controller ICD-13/05 51 of 56• src - Contains VxWorks makefiles which, by default, builds all the *.c, *.st and*.stpp files and

Seite 48

CapFast52 of 56 ICD-13/05 ICD 13—Standard Controllerfile ~p3/wcs/lib/passwd.rc. This file may have more than two lines depending uponhow many CapFast

Seite 49

CapFastICD 13—Standard Controller ICD-13/05 53 of 56Appendix A Address MapsThe VMEbus supports several independent address spaces which have different

Seite 50 - 19.3.2 Directory Structure

CapFast54 of 56 ICD-13/05 ICD 13—Standard ControllerTABLE 32. Standard Controller VME A16 Address SpaceStart End Card4000 403F BC6354100 411F VMI4100[

Seite 51 - 20.0 CapFast

CapFastICD 13—Standard Controller ICD-13/05 55 of 56TABLE 33. Standard Controller VME A24 Address SpaceStart End Card000000 00FFFF XVME-566SE[0]010000

Seite 52

CapFast56 of 56 ICD-13/05 ICD 13—Standard Controller

Seite 53 - Appendix A Address Maps

Standard Controller Information6 of 56 ICD-13/05 ICD 13—Standard Controller2.3 Manufacturers and SuppliersThis section lists the names, addresses and

Seite 54 - Start End Card

Standard Controller InformationICD 13—Standard Controller ICD-13/05 7 of 56[E] Systems Integration Plus, Inc17350 N. Hartford DriveScottsdale,Az 85255

Seite 55 - /05 55 of 56

Standard Controller Information8 of 56 ICD-13/05 ICD 13—Standard Controller[O] Dean MicrosystemsAcal Electronics houseWokingham RoadBracknellBerks.RG1

Seite 56

Hardware InstallationICD 13—Standard Controller ICD-13/05 9 of 563.0 Hardware InstallationThe next sections describe how to set up and test the hardwa